Solar input+Battery input+AC generator input to 3 phase 120kw power inverter
Technical Features:
1) Using the sixth generation efficient IPM intelligent module from Japanese Mitsubishi, high efficiency and stable performance. It with powerful protection function, the protection for short circuit, over load, over temperature is more safe and reliable. It's service life can up to 15 years or more.
2) Two kinds of start mode: Reduction Voltage Start and Variable Frequency Start. Customers can set start mode according to the type of their load. This function is very convenient for users and also reduce frequency converter's usage, which reduced the cost of equipment investment, easy to connect wires and control.
3) Pure sine wave output with good transient response less than 50ms, waveform distortion is very little, higher conversion efficiency and stable output voltage.
4) Adopted low frequency transformer which ensure the input voltage and output voltage are completely electrical isolated to avoid interference.
5) Using SVPWM space vector algorithms, high conversion efficiency, high instantaneous power and low losses conversion efficiency up to 94%.
6) Output AC Power is suitable for all types of electric appliances, electric tools, electric motors etc. higher capability of driving load.
7) Converter has the function of filtering the grid disturbance and interference at the same time, which is a good performance of stabilized voltage and frequency power, to provide a more stable and pure power supply environment for the backend devices.
8) Output perfect protection function, with output over-voltage, overload, short circuit, over temperature, self-diagnosis protection and other protection.
9) High conversion efficiency, high instantaneous power and low load loss.
10) The input voltage, output voltage, frequency and phase can be custom made.
Model |
BZP-120KW |
BZP-150KW |
Isolation mode |
Low Frequency Transformer |
DC Input |
Rated voltage (Vdc) |
480V |
Rated current(A) |
250A |
312.5A |
AC Output |
Rated output power |
120KW |
150KW |
Output waveform |
Pure Sine Wave |
Rated Voltage |
380VAC±3% |
380VAC±3% |
Phases |
3 phase 4 wire |
3 phase 4 wire |
Rated current(A) |
182A (phase current) |
227A (phase current) |
Frequency |
50Hz or 60Hz |
Rated output voltage range (V) |
380/400/415/440VAC optional |
Power Factor(PF) |
1 |
Overload Ability |
150%, 5 seconds |
Efficiency |
>93% |
Waveform distortion rate (THD) |
<3%(Linear load) |
Dynamic Response (0 to 100% load) |
5%,≤50ms |
Display |
LCD |
Running mode |
Working continuously |
Electrical insulation properties |
2000Vac, 1 Minute |
Communication interface (optional) |
RS485 |
Protection Function |
Protection |
Input reverse polarity, under voltage, overvoltage, output over-current, short circuit, overheating etc. |
Cooling method |
Fan-cooled |
Short-circuit protection |
No automatic recovery, need to restart the machine |
Working environment |
Noise ( 1 meter) |
≤100dB |
Degree of protection |
IP20(indoor) |
Working Altitude(m) |
≤2000 |
Working temperature |
-25~+50ºC |
relative humidity |
0~90%,non-condensing |
Mechanical dimension |
Depth* Width * Height |
900x1100x1600mm |
Weight (Kg) |
700Kg |
900Kg |