Phase: | Three Phase |
---|---|
Type: | On-line |
Protection: | Overvoltage |
Model |
HP9330C 20-80KVA | ||||||
20K | 20K-XL | 30K-XL | 40K-XL | 60K-XL ISO | 80K-XL ISO | ||
Rated Capacity | 20KVA/16KW | 30KVA/24KW | 40KVA/32KW | 60KVA/48KW | 80KVA/64KW | ||
Rated Voltage | 380/400/415VAC Three-phase 4 line + earth line | ||||||
Rated Frequency | 50/60HZ | ||||||
Input |
|||||||
Voltage range | 380VAC±25% | ||||||
Frequency range | 50/60HZ±5% | ||||||
Cable Mode | Twin- channel line input | ||||||
THDI | <3% | ||||||
Power factor | >0.99 | ||||||
Output |
|||||||
Voltage precision | 380VAC (±1%),Three-phase 4 line + earth line | ||||||
Frequency precision | 50/60HZ±0.2% | ||||||
Power factor | 0.8 | ||||||
Current crest ratio | 3:1 | ||||||
Overload capacity | ≤110%for 60 minutes,≤125% for 10min,≤150% for 1min | ||||||
Battery |
|||||||
Charging current | 0.5~4.5A(adjustable) | ||||||
Backup time | 7mins | Determined by the amount of external-connected cells | |||||
Quantity | 28/30/32(selective),compatible to battery share in the parallel mode | ||||||
Efficiency | |||||||
Line mode/BAT mode | 94% | ||||||
ECO mode | 98% | ||||||
Indication |
|||||||
LCD | I/O voltage, current, frequency, BAT voltage, charging current value, discharging current value, fault display, fault, warning | ||||||
Communications |
|||||||
Communication interface |
RS232,AS400,RS485,Service,EPO,BAT temperature compensation, Intelligent Slot ,SNMP(Option) |
||||||
Operation Environment | |||||||
Temperature | 0~40°C | ||||||
Humidity |
0~95% (no dewfall) | ||||||
Storage temperature |
-25°C~55°C | ||||||
Altitude(M) |
More then elevation 1500m | ||||||
Weight |
|||||||
weight(KG) | Net weight |
182.5 | 82 | 110 | 114 | 282 | 306 |
Gross weight |
204 | 122 | 160 | 164 | 356 | 380 | |
Dimension (WXDXH)mm |
420 X630 X1240 | 420 X630 X950 | 490 X680 X1180 | 600 X800 X1850 |