Customization: | Available |
---|---|
Output Type: | DC Output |
Warranty: | 1 Year |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
"BZA" series intelligent high-frequency switch power supply modules are specially developed to meet the demands of modern DC system. The charger rectifiers are designed with world leading patent technology "resonant voltage type soft switching power supply technology". They feature high efficiency and stability, intelligent control, small size and light weight.
24VDC rectifier for Telecom Power
|
||||
|
24V20A
|
24V30A
|
24V150A
|
24V200A
|
Input voltage
|
220VAC(-15%~+15%)
|
380VAC(-15%~+15%)
|
||
Output voltage
|
20-29VDC
|
|||
Output current(A)
|
2-20
|
3-30
|
15-150
|
20-200
|
Power(kW)
|
0.6
|
0.9
|
4.5
|
6
|
Size (H × W × D) mm
|
179×109×260
|
230×130×325
|
132×440×400
|
|
Weight(kg)
|
7.2
|
8
|
20
|
20
|
Cooling method
|
Natural Cooling
|
Fan Cooling
|
||
Noise(dB)
|
50
|
|||
Efficiency
|
≥92%
|
|||
Current stabilization
|
<±1%
|
|||
Voltage stabilization
|
<±0.5%
|
|||
Current imbalance in parallel operation
|
≤ ± 3%
|
|||
Communication protocol
|
MODBUS with RS485
|
|||
Operation ambient temperature
|
-10°C ~ 40ºC
|
|||
Storage temperature
|
-40°C~ 60ºC
|
|||
Time delay of start-up
|
3~8s
|
|||
Ripple factor
|
≤0.2%
|
|||
Automatic current limiting
|
When output is over the limit value, the output current will not increase and keep constant current output.
|
|||
Output overvoltage protection function
|
When output voltage exceeds 60-63VDC, then it will switch off output to prevent the equipment broken
|
|
||
Output short circuit protection
|
When output short circuit, the module draws the output voltage to 0 immediately.
The module will resume when the short circuit disappear. |
|||
Insulating strength
|
When output short circuit, the module draws the output voltage to 0 immediately.
The module will resume when the short circuit disappear. |
48VDC rectifier for Telecom Power--1 phase
|
||||
|
48V10A-220
|
48V20A-220
|
48V30A-220
|
48V30A-N
|
Input voltage
|
220VAC (-15%~+15%)
|
|||
Output voltage
|
40-58VDC
|
|||
Output current(A)
|
1-10
|
2-20
|
3-30
|
3-30
|
Power(kW)
|
0.6
|
1.2
|
1.8
|
1.8
|
Size (H × W × D) mm
|
230×130×325
|
179×109×206
|
230×130×325
|
230×130×325
|
Weight(kg)
|
7.7
|
7.7
|
8
|
8
|
Cooling method
|
Natural Cooling
|
Fan Cooling
|
||
Noise(dB)
|
50
|
|||
Efficiency
|
≥92%
|
|||
Current stabilization
|
<±1%
|
|||
Voltage stabilization
|
<±0.5%
|
|||
Current imbalance in parallel operation
|
≤ ± 3%
|
|||
Communication protocol
|
MODBUS with RS485
|
|||
Operation ambient temperature
|
-10°C ~ 40ºC
|
|||
Storage temperature
|
-40°C~ 60ºC
|
|||
Time delay of start-up
|
3~8s
|
|||
Ripple factor
|
≤0.2%
|
|||
Automatic current limiting
|
When output is over the limit value, the output current will not increase and keep constant current output.
|
|||
Output overvoltage protection function
|
When output voltage exceeds 60-63VDC, then it will switch off output to prevent the equipment broken
|
|||
Output short circuit protection
|
When output short circuit, the module draws the output voltage to 0 immediately.
The module will resume when the short circuit disappear.
|
|||
Insulating strength
|
lnput to housing (earth) 1500VAC 1minute 5mA, no breakdown, no flashover
Input to output 1500VAC 1minute 4mA, no breakdown, no flashover
Output to housing (earth) 500VAC 1minute 4mA, no breakdown, no flashover
|
48VDC rectifier for Telecom Power--3 phases
|
||||
|
48T50A
|
48T100A
|
48T150A
|
48T200A
|
Input voltage
|
380VAC(-15%~+15%)
|
|||
Output voltage
|
40-58VDC
|
|||
Output current(A)
|
5-50
|
10-100
|
15-150
|
20-200
|
Power(kW)
|
3
|
6
|
9
|
12
|
Size (H × W × D) mm
|
230×130×325
|
132×440×400
|
||
Weight(kg)
|
8
|
21
|
22.5
|
22.5
|
Cooling method
|
Natural Cooling
|
Fan Cooling
|
||
Noise(dB)
|
50
|
|||
Efficiency
|
≥92%
|
|||
Current stabilization
|
<±1%
|
|||
Voltage stabilization
|
<±0.5%
|
|||
Current imbalance in parallel operation
|
≤ ± 3%
|
|||
Communication protocol
|
MODBUS with RS485
|
|||
Operation ambient temperature
|
-10°C ~ 40ºC
|
|||
Storage temperature
|
-40°C~ 60ºC
|
|||
Time delay of start-up
|
3~8s
|
|||
Ripple factor
|
≤0.2%
|
|||
Automatic current limiting
|
When output is over the limit value, the output current will not increase and keep constant current output.
|
|||
Output overvoltage protection function
|
When output voltage exceeds 60-63VDC, then it will switch off output to prevent the equipment broken
|
|||
Output short circuit protection
|
When output short circuit, the module draws the output voltage to 0 immediately.
The module will resume when the short circuit disappear.
|
|||
Insulating strength
|
lnput to housing (earth) 1500VAC 1minute 5mA, no breakdown, no flashover
Input to output 1500VAC 1minute 4mA, no breakdown, no flashover
Output to housing (earth) 500VAC 1minute 4mA, no breakdown, no flashover
|