Nature of Source Flow: | Active Inverter |
---|---|
Certification: | ISO9001, UL, CE, SAA, UL1741 & CSA22.2 |
Output Power: | >1000W |
Grid Type: | off-Grid Inverter |
Output Type: | Multiple |
Circuit Topologies: | Full-Bridge Type |
Customization: |
---|
Suppliers with verified business licenses
(Below parameter only for reference,Could be custom made to user specifications.)
Model |
BZP-10KW |
|||
Isolation mode |
Low Frequency Transformer |
|||
DC Input |
Rated voltage (Vdc) |
180-550V |
480-850V |
|
Rated current(A) |
45A |
17A |
||
AC Output |
Rated output power |
10KW |
||
Output waveform |
Pure Sine Wave |
|||
Rated Voltage |
220V±3% |
110/220V or 120/240V |
380VAC±3% |
|
Phases |
Single phase |
split phase |
3 phase 4 wire |
|
Rated current(A) |
45.5A |
45.5A(phase current) |
15A (phase current) |
|
Frequency |
50Hz or 60Hz |
|||
Rated output voltage range (V) |
110/120/220/230/240/380/400/415VAC optional |
|||
Power Factor(PF) |
1 |
|||
Overload Ability |
150%, 5 seconds |
|||
Efficiency |
>93% |
|||
Waveform distortion rate (THD) |
<3%(linear load="" span=""> |
|||
Dynamic Response (0 to 100% load) |
5%,≤50ms |
|||
Display |
LCD |
|||
Running mode |
Working continuously |
|||
Electrical insulation properties |
2000Vac, 1 Minute |
|||
Protection Function |
Protection |
Input reverse polarity, under voltage, overvoltage, output over-current, short circuit, overheating etc. |
||
Cooling method |
Fan-cooled |
|||
Short-circuit protection |
No automatic recovery, need to restart the machine |
|||
Working environment |
Noise ( 1 meter) |
≤50dB |
||
Degree of protection |
IP20(indoor) |
|||
Working Altitude(m) |
≤2000 |
|||
Working temperature |
-25~+55ºC |
|||
relative humidity |
0~90%,non-condensing |
|||
Mechanical dimension |
Depth* Width * Height |
550x550x860mm |
||
Weight (Kg) |
110Kg |
Suppliers with verified business licenses