Category | Name | Parameter |
Environmental conditions | Operation temperature | -40°C ~ +75°C, derating is require when the temperature is above 55°C. |
Storage temperature | -40°C ~ +70°C | |
Relative humidity | ≤95%RH, without condensation | |
Cooling mode | Forced air cooling | |
Altitude | 2,000 m a.s.l., derating is require when the altitude is above 2,000 m a.s.l. | |
Atmospheric pressure | 79 kPa ~ 106 kPa | |
AC input | Input system | Three phases + PE |
Voltage range | 260 Vac ~ 530 Vac | |
The maximum static voltage borne under no operation | 600 Vac | |
Rated voltage | 400 Vac | |
Maximum current | 32A | |
Grid frequency | 45 Hz~ 65 Hz | |
Rated frequency | 50Hz/60Hz | |
DC output | Voltage range | 50 Vdc ~ 750Vdc |
Current range | 0 ~ 33.3A (high voltage)/ 0~50A(low voltage) | |
Rated current | 26A@750V (required for setting of current limiting point,750V is 26.67A) | |
Steady voltage precision | <±0.5% | |
Steady current precision | ≤±1% (rated range of 20% ~ 100% for output load) | |
Load regulation rate | ≤±0.5% | |
Grid regulation rate | ≤±0.1% (testing range is 320V ~ 530V) | |
Startup overshoot | ≤±3% | |
Peak-to-peak value noise | ≤1% (150~750V, 0~20MHz) | |
Power factor and THD | Power factor | ≥0.95 Full-load output power of @20%~50% |
≥0.98 Full-load output power of @50%~100% | ||
≥0.99 Full-load output power, input nominal voltage and frequency of @100% | ||
THD | ≤5% Full-load output power of @50%~100% | |
Efficiency | Under Rated input voltage | ≥95.2%,@750V,50%~100% |
EMC | Emission | ClassA , Meet the requiremnt of NB/T 33001-1-2010,NB/T 33008-1-2013 |
Immunity | C lassA , Meet the requiremnt of NB/T 33001-1-2010,NB/T 33008-1-2013 | |
Other | Instant impulse current upon startup | <45A |
Current sharing | In case of load of 10%~100%, the module current sharing error ≤ rated output current of ±5%. | |
Noise | ≤65dB(1m away, | |
Startup duration (select the startup mode through the monitoring module) | Normal startup mode: the time delay from AC power-on to module output is ≤ 8s. | |
Output delayed startup: The startup duration can be set through the monitoring module, with default output startup duration of 3~8s. | ||
Earthing resistance | Earthing resistance ≤ 0.1Ω, bearable current ≥ 25A | |
Surge protection | Meets IEEE C62 41-1991 Class B3 rating, 6kV/3kA (1.2/50μs impulse voltage and 8/20μs inrush current mixed wave) | |
Insulation resistance | The insulation resistance of DC part and AC part to housing and the AC part to the DC part shall be ≥ 10MΩ. | |
Insulation strength | AC input terminal to the housing 3535V DC voltage 20S clock, no breakdown, no arcing phenomenon, steady state leakage current is less than 1mA; AC input terminal to DC output terminal 3535V DC voltage 20S clock, no breakdown, no arcing phenomenon, steady-state leakage current is less than 1mA; DC output terminal to the housing 3535V DC voltage 20S clock, no breakdown, no arcing phenomenon, steady state leakage current is less than 1mA; |
|
ROHS | R5 | |
Mechanical parameters | Size | 84Mm (H) ×226mm (W) ×395mm (D) |