Operation | Control mode | Keyboard/extermal terminal/RS485 communication | |||
Starting mode | Current limiting/voltage/keavy load | ||||
Start and stop time | Can be set digitally | ||||
Start delay | Can be set digitally | ||||
Emergency stop | Stop the output of the soft starter | ||||
Limiting current | The starting current should be lower than the limiting current if the soft starter is operating under current limiting or heavy load mode | ||||
Starting voltage | The starting voltage can be set digitally if the soft starter is operating under voltage mode | ||||
Load control | Possibility to check accidents including belt tripping | ||||
Autonmatic restart | Autonmatic restart after breakdown | ||||
Fault output | Contact output AC 250V 1A ;DC30V 1A | ||||
Multi-function relay output | Start delay, Start,Operation,Stop,Full stop restart | ||||
Analogue output | 0~20mA / 4~20mA available | ||||
Portection function | Portection of soft starter | Protecting from overload,overcurrent,overheat,unbalanced three phase,missing phase,under loading,extemal fault,etc | |||
Warning of soft starter | Emergency stop,under loading,restart,etc | ||||
Display | Keyboard | Operation information | Operation,stop and fault warnings during standby,start delay and starting | ||
Protection | Protect the parameters from being modified | ||||
Application conditions | Application category | AC-53b | |||
Rated insulation voltage | 660V | Rated impulse withstand voltage | 4KV | ||
Protection degree | IP20 | ||||
Environment conditions | Ambient temperature | -10ºC~40ºC | |||
Storage temperature | -20ºC~65ºC | ||||
Storage temperature | Maximum90%RH(No condensation) | ||||
Ambient humidity | Below 1000m;below 5.9m/s(=0.6g) | ||||
Altitude/vibration | Without corrosive gas,flammable gas,oil mist,dust or others | ||||
Cooling | Natural air cooling |
MODEL | Rated power (kW) |
Rated current (A) |
Compatible circuit breaker(QF) | Compatible bypass contactor(KM) | Cable specification |
BZ1S23T4 | 11 | 23 | CM1-63L/32 | CJ20-25 | 6mm2 cable |
BZ1S30T4 | 15 | 30 | CM1-63L/40 | CJ20-40 | 10mm2 cable |
BZ1S37T4 | 18.5 | 37 | CM1-63L/40 | CJ20-40 | 16mm2 cable |
BZ1S45T4 | 22 | 45 | CM1-63L/63 | CJ20-63 | 16mm2 cable |
BZ1S60T4 | 30 | 60 | CM1-100L/80 | CJ20-63 | 25mm2 cable |
BZ1S75T4 | 37 | 75 | CM1-100L/100 | CJ20-100 | 35mm2 cable |
BZ1S90T4 | 45 | 90 | CM1-225L/125 | CJ20-100 | 35mm2 cable |
BZ1S110T4 | 55 | 110 | CM1-225L/160 | CJ20-160 | 35mm2 cable |
BZ1S145T4 | 75 | 145 | CM1-225L/180 | CJ20-160 | 35mm2 cable |
BZ1S175T4 | 90 | 175 | CM1-225L/200 | CJ20-250 | 30*3mm2copper row |
BZ1S210T4 | 110 | 210 | CM1-400L/250 | CJ20-250 | 30*3mm2copper row |
BZ1S250T4 | 132 | 250 | CM1-400L/315 | CJ20-400 | 30*4mm2copper row |
BZ1S300T4 | 160 | 300 | CM1-400L/350 | CJ20-400 | 30*4mm2copper row |
BZ1S370T4 | 200 | 370 | CM1-400L/400 | CJ20-400 | 40*4mm2copper row |
BZ1S470T4 | 250 | 470 | CM1-630L/630 | CJ20-630 | 40*5mm2copper row |
BZ1S570T4 | 315 | 570 | CM1-800H/700 | CJ40-800 | 40*5mm2copper row |
BZ1S720T4 | 400 | 720 | CM1-800H/800 | CJ40-1000 | 50*5mm2copper row |
BZ1S840T4 | 450 | 840 | CM1-1250/1000 | CJ40-1000 | 50*5mm2copper row |
Type | Symbol | Name | Description | |
Main circuit | R,S,T | AC power input of the main circuit | Connect with 3-phase power supply through circuit breaker | |
U,V,W | Output terminal of the soft starter | Connect with 3-phase asynchronous motor | ||
L1,L2,L3 | Specific terminal for external bypass contactor | Connect with bypass contactor | ||
Control power supply | 12 | Terminal for control power supply input | Connect with AC 220V, 50Hz | |
13 | ||||
Control circuit | Relay output |
1 | Control terminal of bypass contactor Bypass |
Close after starting Capacity AC 220V 5A |
2 | ||||
3 | Fault relay output Break |
Active during fault(Multiple modcs available for choosing) CapacityAC 220V 5A |
||
4 | ||||
5 | Multi-function relay output Chain |
Programmable activity mode CapacityAC 220V 5A |
||
6 | ||||
DIGITAL input | 7 | External reset tenninal RET | External emergency stop signal | |
8 | Control terminal of emergency stop EMS | External reset signal during fault | ||
9 | Extemal-control stop terminal STOP | Under external control mode,when STOP and COM is closed,and RUN and COM is closed,operation is active.Otherwise stop is active. | ||
10 | External-control operation terminal RUN | |||
11 | COM terminal of external signal COM | COM terminal of digital input | ||
RS485 Communication |
A- | Positive signal of 485 communication | RS485communication tenminal | |
B+ | Negative signal of 485 communication | |||
GND | GND tenninal | 0-20mA or 4-20mAanalogue output,that can be chosen through programming | ||
FM | Output termmal of current signal |